Safety Topic (Electrical)



ELECTRICAL SAFETY



CARE & MAINTENANCE OF ELECTRICAL PANEL BOARDS

Electrical panel boards are essential to distribute electrical power throughout our buildings and facilities, and they need to be properly maintained and protected to ensure they operate safely. There are many factors that can affect the operation of electrical panel boards and associated circuit breakers, such as the following.
·         Ingress of dust and moisture
·         Corrosion
·         Incorrect installation and positioning
·         Poor care & maintenance
·         Loose terminal connections
·         Overloaded branch circuits, improperly rated circuit breakers to match connected load 
·         Worn-out and obsolete circuit breakers 

1.      Ingress of Dust and Moisture
Water moisture and dust do not mix with electricity. Even when dry, dust inside a panel board can cause electrical tracking and arcing leading to overheating and smoldering fires, and when dust is moist or wet, the problem is even greater. If the panel board has a light covering of dust inside, use a compressed air canister to clean it. But if the dust coating is heavy, turn off the power and isolate the main feeder cable [using log out & tag procedure], and use a dry cloth and a clean paint brush to remove the dust.

Corroded Electrical Terminals


Never use WD40 inside an electrical panel board, if it gets onto the circuit breakers is can seize them solid permanently (this is explained in more detail in item 4 below). There are specialist maintenance aerosol sprays available for cleaning electrical panel boards, but only use weak solvent types and they must have a high-dielectric quality for energized panel boards. Aerosol sprays with a low-dielectric means that the spray mist will conduct electricity and so if used on an energized panel board could result in electric shock, serious injury or worse. Good quality aerosol sprays approved for maintenance of electrical panel boards usually have a water moisture ‘expellant’ property, which means they will disperse moisture and water from electrical connections. Aerosol sprays with a strong solvent will damage circuit breakers, so any aerosol sprays for panel board maintenance must be approved by CS AAS/SCG before use.   

2.      Corrosion
Water, moisture and condensation cause corrosion damage to circuit breakers, electrical connections and electrical panel board steel enclosures. Corroded circuit breakers are often stuck up and seized solid, which means they will not operate in an electrical short circuit or emergency and in the past serious fires have occurred as a result. Corrosion on electrical terminals can cause bad connections, resulting on loss of service, arcing, overheating and fire. Corrosion on panel board steel enclosures, can be so severe it causes the entire unit to fall apart leading to a serious electrical safety hazard.

Corroded Circuit Breaker

All electrical equipment is rated for the type of service application, such as indoor service, external/dry, external/wet areas, etc, by International Standard IEC 60529: Ingress Protection Rating [IP rating] for electrical equipment, Table 2.1 below shows the rating for each application, and indoor electrical panel boards generally have an ingress protection rating of IP40 [no protection from water/moisture], while electrical panel boards for occasional moist areas [such as kitchens] are IP54, and electrical panel boards exposed to water or rain, need to be IP64/65. So water, moisture and condensation should be kept away from electrical panel boards that have the regular IP40 rating. Corrosion has occurred in the following areas.
A.    Indoor electrical panel boards in an air-conditioned area, moisture can get into the enclosure via the electrical service conduit from the outside or via conduits connecting to non-air-conditioned ceiling voids, etc. This can be easily corrected by applying silicone sealant the conduits entry points within the enclosure.

B.     Electrical panel boards are often located in mechanical rooms of houses and buildings, and in most cases the mechanical room is an open plenum for the air-conditioning return air. If the mechanical room door to the outside has a bad seal, warm moist air will enter causing condensation on the outside and inside of the electrical panel board. This can be easily corrected by repairing/replacing the mechanical room door seals.    

Corroded Electrical Panel Board

Table 2.1 - International Standard IEC 60529
Ingress Protection Rating [IP rating] for electrical equipment
Solids, first digitthe first digit indicates the level of protection that the enclosure provides against access to hazardous parts (e.g., electrical conductors, moving parts) and the ingress of solid foreign objects.
Level
Object size protected against
Effective against
0
No protection against contact and ingress of objects
1
>50 mm
Any large surface of the body, such as the back of a hand, but no protection against deliberate contact with a body part
2
>12.5 mm
Fingers or similar objects
3
>2.5 mm
Tools, thick wires, etc.
4
>1 mm
Most wires, screws, etc.
5
Dust protected
Ingress of dust is not entirely prevented, but it must not enter in sufficient quantity to interfere with the satisfactory operation of the equipment; complete protection against contact
6
Dust tight
No ingress of dust; complete protection against contact

Liquids, second digit – protection of the equipment inside the enclosure against harmful ingress of water

Level
Protected against
Testing for
0
Not protected
1
Dripping water
Dripping water (vertically falling drops) shall have no harmful effect.
2
Dripping water when tilted up to 15°
Vertically dripping water shall have no harmful effect when the enclosure is tilted at an angle up to 15° from its normal position.
3
Spraying water
Water falling as a spray at any angle up to 60° from the vertical shall have no harmful effect.
4
Splashing water
Water splashing against the enclosure from any direction shall have no harmful effect.
5
Water jets
Water projected by a nozzle (6.3mm) against enclosure from any direction shall have no harmful effects.
6
Powerful water jets
Water projected in powerful jets (12.5mm nozzle) against the enclosure from any direction shall have no harmful effects.
7
Immersion up to 1 m
Ingress of water in harmful quantity shall not be possible when the enclosure is immersed in water under defined conditions of pressure and time (up to 1 m of submersion).
8
Immersion beyond 1 m
The equipment is suitable for continuous immersion in water under conditions which shall be specified by the manufacturer.

3.      Incorrect Installation and Positioning
Electrical panel boards are often installed in the incorrect location, such as dust and moisture enters an IP40 rated panel board in a located garage, storehouse or similar, where building doors are frequently opened; the correct type of panel board enclosure for this purpose is IP54 [splash and dust resistant, subjected to occasional moisture] see Table 2.1 above.

An IP54 rated panel board is located in a frequently wetted area, such as pump room, swimming pool area, etc, the correct type of panel board enclosure for this purpose is IP64/65, see Table 2.1 above. 

4.      Poor Care & Maintenance
A circuit breaker is a thermo-electric device, which means it has an internal spring device attached to a small electric heating element, and when the electrical current in the circuit exceeds the circuit-breaker rated value, the heating element releases the spring and quickly turns off the electrical power. The circuit-breaker spring device is lubricated with dielectric grease, but the circuit breaker toggle switch still needs to be operated periodically [annually minimum] to ensure free movement. 

Poorly Maintained Circuit Breakers


The WD40 aerosol maintenance spray has been commonly used in electrical maintenance for several decades, and it has good water moisture expellant properties, it is a high-dielectric so does not conduct electricity, and also a good solvent cleaner/degreaser for electrical contacts and terminals. The active ingredient in WD40 is naphtha [volatile hydrocarbon], which makes it very quick drying. But naphtha is also a very strong solvent which means it will quickly dissolve the dielectric grease inside circuit breakers, and they will become stuck up and seized quickly afterwards. This is why WD40 must never be used, as most circuit breakers are sealed devices and so the dielectric grease cannot be replaced. All aerosol sprays for panel board maintenance must be approved by CS AAS/SCG before use.

5.      Loose Terminal Connections
Loose electrical terminal connections on circuit breakers can result in loss or service, arcing, overheating and outbreak of fire, so it is very important to retighten the connections periodically [annually minimum]. The terminals on the branch circuits need to be de-energized using the main breaker before tightening, and the terminals on the main breaker, isolate the main feeder cable [using log out & tag procedure] before attempting to retighten the terminals.    


6.      Overloaded Branch Circuits
Improperly sized or rated circuit breakers to match connected load will often cause frequent tripping incidents and early failure of the breaker. The rating and sizing of circuit breakers shall be in accordance with NEC, but a good rule of thumb is to select breakers 140% (minimum) of the full load current in resistive circuits [lighting, convection heaters, electronic devices, cooking appliances, etc]; and 130% (minimum) of the startup current of inductive loads [fan motors, pumps, fan-assisted heaters, compressors, etc], this avoids frequent nuisance tripping incidents and early failures.        


7.      Worn-Out and Obsolete Circuit Breakers 

As mentioned earlier in item 4 above, a thermo-electric circuit breaker has an internal mechanical spring, which weakens and wears out with age. Five (5) years after installation the spring will have lost some of its tension ability, and by ten (10) years a significant portion of the tension ability may have been lost. This means the circuit breaker may not reset correctly after tripping, or more importantly may not operate and safely disconnect the electrical current during overload conditions as originally designed by the manufacturer. Accordingly, electrical panel board circuit breakers need to be replaced with new ten (10) years after the installation date, or when the building is renovated, whichever is the sooner. For larger more expensive circuit breakers, a full load and function test in accordance with the manufacturer’s instructions needs to be carried out to determine whether the breaker disconnection time still complies with the design specification, or replace the entire breaker, whichever is the most feasible and cost effective.          

                                                          Update:20- Jan -2016

REFERENCE




No comments

Pinterest Gallery